MTHW Pipe Freezing at UCLH Hospital, London

Our team completed four liquid nitrogen pipe freezes at UCLH Hospital, enabling the replacement of a leaking MTHW heating valve without draining the entire system.

Project at a Glance

Client: Mitie
Location: University College London Hospital (UCLH), London NW1
Service: Liquid Nitrogen Pipe Freezing
Pipework: Medium Temperature Hot Water (MTHW) steel pipework
Sector: Healthcare and Hospital Facilities
Works Included: Four MTHW pipe freezes (three 6-inch and one 2½-inch), temporary pipe isolation to enable leaking valve replacement without draining the heating system.

Pipe Freezing for Heating Valve Replacement

We successfully completed four liquid nitrogen pipe freezes at University College London Hospital (UCLH) in London on behalf of our Mitie. The project involved isolating Medium Temperature Hot Water (MTHW) steel pipework on the fourth-floor podium to allow engineers to replace a valve that leaking.

The existing valve was letting-by, preventing effective isolation of the affected pipework. Rather than drain down the full heating system, the site team chose specialist pipe freezing to provide temporary isolation. Our engineers attended the hospital on a Saturday, outside normal working hours, to carry out the work.

Pipe Freeze on the MTHW pipework in London

Why was Pipe Freezing Required?

The leaking valve required replacement, but draining the heating system was not the preferred option. Liquid nitrogen pipe freezing offered a time-saving, cost-effective alternative by creating temporary ice plugs to isolate the affected pipework.

However, the MTHW pipework needed careful preparation before freezing could begin. The site maintenance team isolated the boilers in advance to allow the water temperature to fall to ambient or below. They also stopped the pumps and confirmed there was no water circulation. These conditions were essential because flowing water can prevent stable ice plugs from forming.

How did our Engineers Complete the Four Pipe Freezes?

Our specialist engineers accessed the MTHW steel pipework and removed sections of insulation at the designated freezing points.

Using liquid nitrogen and specialist pipe freezing jackets, the team successfully completed:

  • Three 6-inch pipe freezes
  • One 2½-inch pipe freezes

Once the ice plugs formed, they provided temporary isolation while other engineers replaced the leaking valve and reconnected the pipework. Following the valve replacement, our team allowed the ice plugs to thaw, checked for leaks and reinstated the pipework insulation. The site maintenance team then reinstated the boilers and pumps.

MTHW Pipe Freeze in London

Heating Valve Replacement Without Draining the System

Our engineers maintained four temporary ice plugs within the MTHW pipework while others replaced the leaking valve and reconnected the system. Following the valve replacement, our team allowed the ice plugs to thaw, checked for leaks and reinstated the pipework insulation.

Project Results

IDWe Pipe Freezing completed the works at UCLH Hospital, providing temporary isolation without the need for a full heating system drain down.

Key outcomes included:

  • Four liquid nitrogen pipe freezes completed on MTHW steel pipework
  • Leaking heating valve replaced by others
  • Full heating system drain down avoided
  • Works completed on a Saturday, outside normal working hours

The project highlights how specialist pipe freezing can support planned maintenance and valve replacement in complex healthcare environments.

PIpe Freezing Services London

Related Hospital Pipe Freezing Projects

Discover how we have supported heating system repairs, valve replacements and essential pipework maintenance across other hospitals.

Pipe Freezing at Whittington Hospital, London

Our engineers completed two liquid nitrogen pipe freezes on 3-inch LTHW pipework at Whittington Hospital, allowing the replacement of a faulty differential pressure regulating valve (DRV) following a leak – read our Whittington Hospital case study.

Pipework Freezing in Woking, Surrey

Explore another example of our specialist pipe freezing services in Woking, Surrey, supporting pipework maintenance and temporary isolation – read the case study.

 

Frequently Asked Questions for MTHW Pipe Freezing

Can you replace a leaking heating valve without draining the system?

Liquid nitrogen pipe freezing can create temporary ice plugs within suitable heating pipework, allowing engineers to replace valves without draining the entire system. At UCLH Hospital, IDWe completed four pipe freezes to enable the replacement of a leaking MTHW valve.

Why must MTHW pipework cool before pipe freezing?

Engineers must allow Medium Temperature Hot Water (MTHW) pipework to cool sufficiently before creating stable ice plugs. Water circulation must also stop to allow the freeze to form. At UCLH Hospital, the site maintenance team isolated the boilers and pumps before our engineers began work.

Would you be Able to Freeze Large-Diameter MTHW Steel Pipework?

Specialist liquid nitrogen pipe freezing equipment can isolate large-diameter steel pipework when conditions allow. At UCLH Hospital, our engineers successfully froze three 6-inch sections and one 2½-inch section of MTHW steel pipework.

 

Hot Tapping Company London

Specialist Pipe Freezing and Valve Installation Company

Are you planning a heating valve replacement, pipework repairs or essential maintenance within a hospital or healthcare facility?

We provide trusted liquid nitrogen pipe freezing and valve installation services across London and the South East. With over 35 years of engineering experience, we deliver practical pipe isolation solutions for commercial and industrial facilities. We work across London, Kent, Surrey, Hampshire, Essex, East Sussex, West Sussex and beyond.

Our experienced engineers assess each project before recommending an appropriate pipework isolation solution. From planned valve works to complex building-services alterations, we focus on high-quality work and controlled project delivery. As one of London’s established pipe freezing contractors, we understand the demands of working within operational commercial buildings.

Contact us today for:

Talk to our team if you need a trusted pipe freezing contractor for an upcoming project.

Can we help you? Please call 020 8302 7644 or email info@idwe.co.uk.

View all services IDWe Ltd offer

Stay up to date with IDWe Ltd’s latest news and projects. Follow us on:

LinkedIn logo Instagram Facebook X logo